105
Set this parameter after replacing the terminal
block or drive modules.
Default: <2>
Determined by
drive capacity
ENTER Key Function
During Frequency
Command Setting
0 ∶ ENTER Key Required
1 ∶ ENTER Key Not Required
When entering a frequency command, the
output frequency changes immediately by UP or
DOWN key without pressing ENTER.
Action selection
when the LCM
operator is
disconnected
Operation Direction
at Power Up when
Using Keypad
0 ∶ Forward
1 ∶ Reverse
This parameter is enabled only when the keypad is
selected as the Run command source.
Cumulative
Operation Time
Setting
Sets the initial value by 10 hours to start keeping
track of cumulative operation time.
Default: 0 h
Min.: 0 h
Max.: 6000 h
Cooling Fan
Operation Time
Setting
Sets the initial value to start keeping track of
cumulative fan operation time. View the
cumulative fan operation time in U3-01.
Default: 0 h
Min.: 0 h
Max.: 6000 h
Resets the data for U2-□□ (Fault Information) as
these data will not be reset by A1-03 (Reset).
0 ∶ Disabled
1 ∶ Enabled
kWh monitoring
initialization
selection
0: Maintain accumulated power value
1: Reset the accumulated power value
Turn ISA Pro oscilloscope on/off
0 : Close
1 : Open