106
1 ∶ Motor 1
Set details in d1-00 to d1-11, d2-00 to d2-10.
2 ∶ Motor 2
Set details in d1-12 to d1-22, d2-11 to d2-22.
Default∶ 1
Min.: 1
Max.: 2
Auto-Tuning
Method Selection
0 ∶ Rotational Auto-Tuning
1 ∶ Stationary Auto-Tuning
2 ∶ Stationary Auto-Tuning for Line-to-Line
Resistance
Default∶ 0
Min.: 0
Max.: 3
Sets the motor rated output power in kW units.
Note: 1HP (Horse Power) = 0.746kW
Default∶ Determined by
o2-03,A1-06
Min.: 0.00 kW
Max.: 650.00 kW
Sets the motor rated voltage according to the
motor nameplate.
Default∶ Determined by
A1-03
Min.: 0.0 V
Max.: 255.0 V <3>
Sets the motor rated current according to the
motor nameplate.
Default∶ <2>
Min.: 10% of drive
rated current
Max.:200% of drive
rated current
Sets the motor base frequency according to the
motor nameplate.
Default∶ Determined by
A1-03
Min.: 0.0 Hz
Max.: 400.0 Hz
Sets the number of motor poles according to the
motor nameplate.
Default∶ 4
Min.: 2
Max.: 48
Sets the motor base speed according to the motor
nameplate.
Default∶ Determined by
A1-03
Min.: 0 rpm
Max.: 24000 rpm
PG Number of
Pulses Per
Revolution
Sets the number of pulses per revolution for the
PG (pulse generator or encoder).
Default∶ 1024 ppr
Min.: 1 ppr
Max.: 60000 ppr
Motor No-Load
Current (Stationary
Auto-Tuning)
Sets the no-load current for the motor.
After the motor output power and rated current
are set in t1-02 and t1-04, this parameter will
automatically display the no-load current of a
standard motor. The no-load current must be
entered according to the motor test report.
Default∶ Determined by
O2-03, A1-06
Min.: 0.0 A
Max.: Max.: [t1-04] –
0.1