82
Parameter
Name
Description
Setting Range
from the frequency command.
Select the offset frequency in E1-□□= 53, 54 and
55 (Offset Frequency 1 to 3).
Max.: 100.0%
Group d, Motor Parameters
d1: V/F Characteristics
d1-00
Input Voltage
Setting
Sets the input voltage of the drive.
Always set the input voltage of the drive (not
motor) to this parameter.
Default: Defined by
A1-03
Min.: 155V
Max.: 255V <3>
d1-01
V/F Pattern
Selection
0 50 Hz (Constant Torque Characteristic 1)
1 60 Hz (Constant Torque Characteristic 2)
2 60 Hz (Constant Torque Characteristic 3), 50 Hz
base
3 72 Hz (Constant Torque Characteristic 4), 60 Hz
base
4 50 Hz (Derated Torque Characteristic 1)
5 50 Hz (Derated Torque Characteristic 2)
6 60 Hz (Derated Torque Characteristic 3)
7 60 Hz (Derated Torque Characteristic 4)
8 50 Hz (High Starting Torque Characteristic 1)
9 50 Hz (High Starting Torque Characteristic 2)
A 60 Hz(High Starting Torque Characteristic 3)
B 60 Hz(High Starting Torque Characteristic 4)
C 90 Hz, 60 Hz base
D 120 Hz, 60 Hz base
E 180 Hz, 60 Hz base
F 60Hz (Constant Torque Characteristic) (Default)
Default: F
Range: 0 to 9, A to F
d1-02
Maximum Output
Frequency
When d1-01 E, parameters d1-02 to d1-11 can
be used to monitor the V/F pattern.
When d1-01 = F, parameters d1-02 to d1-11 can
be used to create a V/F pattern.
Default: <1>
Min.: 25.0 Hz
Max.: 400.0 Hz
d1-03
Maximum Voltage
Default: <1>
Min.: 0.0 V
Max.: 255.0 V <3>
d1-04
Base Frequency
Default: <1>
Min.: 0.0 Hz
Max.: Defined by d1-02
d1-05
Base Voltage
Default: <1>
Min.: 0.0 V
Max.: 255.0 V <3>