Motor 2 Leakage
Inductance
Sets the motor 2 voltage drop caused by the
motor leakage inductance relative to the motor
rated frequency and current. This will be set
automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.00 mH
Max.:650.00 mH
Sets the motor 2 rotor resistance. This will be set
automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.000 Ω
Max.: 65.000 Ω
Motor 2 Mutual
Inductance
Sets the motor 2 mutual inductance. This will be
set automatically during Auto-Tuning.
Default: o2-03, A1-06
Min.: 0.00 mH
Max.:6500.0 mH
Sets the motor 2 rated capacitor. This will be set
automatically during Auto-Tuning.
Default: o2-03
Min.: 0.00 kW
Max.: 650.00kW
Sets the motor rated capacity.
Default: Determined by
o2-03
Min.: 0.00 kW
Max.: 650.00kW
Sets the motor rated current.
Default: Determined by
o2-03
Min.: 10% of drive
rated current
Max.: 200% of drive
rated current
Sets the number of motor poles.
Default: 6
Min.: 2
Max.: 48
PM Motor Rotor
Resistance (r 1)
Sets the resistance per motor phase in units of
0.001 Ω. Refrain from change once this parameter
is set.
Default: Determined by
o2-03
Min.: 0.000 Ω
Max.: 65.000 Ω
PM Motor d-Axis
Inductance (Ld)
Sets the motor d-axis inductance in units of 0.01
mH. Refrain from change once this parameter is
set.
Default: Determined by
o2-03
Min.: 0.00 mH
Max.: 600.00 mH
PM Motor q-Axis
Inductance (Lq)
Sets the motor q-axis inductance in units of
0.01mH. Refrain from change once this parameter
Default: Determined by
o2-03