88
Parameter
Name
Description
Setting Range
19 Baseblock Command (Normal Open)
20 Baseblock Command (Normal Closed)
21: Fast Stop (Normal Open)
22: Fast Stop (Normal Closed)
23 to 38 : External Fault
39: Fault Reset
40 : oH2 (AC drive Overheat Alarm)
41 : Multi-Function Analog Input Selection
45: Communication Mode
46: PID Disable
47: PID Integral Reset
48: PID Integral Hold
49: PID Soft-Start On/Off
50: PID Input Characteristics Switch
51: Motor 1/2 Switch
52: Timer Input
53, 54, 55: Offset Frequency 1/ 2/ 3
56: KEB Command 1 (Normal Closed)
57: KEB Command 1 (Normal Open)
58: The Traverce Function Up
59: The Traverce Function Down
60: Program Lockout
61: Analog Frequency Command Hold
63: External Speed Search Command
65: DC Braking
69 : Drive Enabled
70: Speed/torque control switching
71: Zero servo command
72~73 : Reserved
100~173: 0~73 inverting output
Max.: 0 ~73 / 100 ~173
E1-06
Terminal S7
Function Selection
Default : 9
Min.: 0
Max.: 0 ~73 / 100 ~173
E1-07
Terminal S8
Function Selection
Default : 19
Min.: 0
Max.: 0 ~73 / 100 ~173
E1-08
<9>
2/3-wire control
switching line
control switching
0 : 2/3 line control mode 1
1 : 2/3 line control mode 2
Default : 0
Min.: 0
Max.: 1
E1-09
DI terminal delay
time
It is used to set the delay time of the inverter
when the status of the DI terminal changes.
Default : 5ms
Min.: 0
Max.: 500ms
E2: Multi-Function Digital Output
E2-00
Relay 1 Function
Selection
0 : During Run
1 : Zero Speed
2 : Frequency (Speed) Agree
3 :User-Defined Frequency (Speed ) Agree
Default: 11
Range: 0 to 49 / 100 to
149
E2-01
Relay 2 Function
Default: 0