90
Parameter
Name
Description
Setting Range
E2-05
Watt Hour Output
Unit
Selects the output unit for the terminal assigned
to E2-00 or E2-03=37 for one pulse signal.
0: 0.1 kWh units
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 0
Range: 0 to 4
E2-06
<7>
Relay 1 conduction
delay time
Define the conduction delay time setting of relay
1
Default: 0.0 s
Min.: 0.0 s
Max.: 3600.0 s
E2-07
<7>
Relay 1 release
delay time
Define the output release delay time setting for
relay 1.
Default: 0.0 s
Min.: 0.0 s
Max.: 3600.0 s
E2-08
<7>
Relay 2 conduction
delay time
Define the conduction delay time setting of relay
2
Default: 0.0 s
Min.: 0.0 s
Max.: 3600.0 s
E2-09
<7>
Relay 2 release
delay time
Define the output release delay time setting for
relay 2
Default: 0.0 s
Min.: 0.0 s
Max.: 3600.0 s
E3: Multi-Function Analog Input
E3-00
Terminal A1 Signal
Level Selection
0 0 to 10 V
1 -10 to 10 V
Default: 0
Range: 0, 1
E3-01
Terminal A1
Function Selection
0 : Main Frequency Command
1 : Frequency Gain
2 : Output Frequency Lower Limit
3 : Auxiliary Frequency Command
4 : Output Voltage Bias
5 : Acc./Dec. Time Gain (Decrease Only)
6 : DC Braking (DB) Current
7 : Stall Prevention Level During Run
8 : PID Feedback
9 : PID Target
10: Differential PID Feedback
11 : Overtorque/ Undertorque Detection
12, 13, 14, 17 : Forward/Reverse/Regeneration
Range/Forward and Reverse Torque Limit
18: Communication Mode 1
19 : Communication Mode 2
20: VF separation voltage
21: No function
Default: 0
Range: 0 to 21