91
Parameter
Name
Description
Setting Range
E3-02
<4>
Terminal A1 Input
Gain
Sets the terminal A1 input gain as a percentage
when inputting 10V
Default: 100.0 %
Min.: -999.9 %
Max.: 999.9 %
E3-03
<4>
Terminal A1 Input
Voltage Bias
Sets the terminal A1 input voltage bias as a
percentage when inputting 0V
Default: 0.0 %
Min.: -999.9 %
Max.: 999.9 %
E3-04
Retain
E3-05
Terminal A1 Input
Filter Time
Sets the terminal A1 primary delay filter time,
which can eliminate the interference
Default: 0.20 s
Min.: 0.00 s
Max.: 2.00 s
E3-06
Terminal A2 Signal
Level Selection
0 : 0 to 20 mA
1 : 4 to 20 mA
2 : 0 to 10 V
3 : 0 to 5 V
Default: 1
Range: 0, 1, 2, 3
E3-07
Terminal A2
Function Selection
0 : Main Frequency Command
1 : Frequency Gain
2 : Output Frequency Lower Limit
3 : Auxiliary Frequency Command
4 : Output Voltage Bias
5 : Acc./Dec. Time Gain (Decrease Only)
6 : DC Braking (DB) Current
7 : Stall Prevention Level During Run
8 : PID Feedback 9 : PID Target Value
10: Differential PID Feedback
11 : Overtorque/Undertorque Detection
12, 13, 14, 17 : Forward/Reverse /Regeneration
Range/ Forward and Reverse Torque Limit
15: Torque Limit Using Torque Command/ Speed
Limit
16: Slip Compensation
18, 19 :Communication Mode
20: VF separation voltage
21: No function
Default: 8
Range: 0 to 21
E3-08
<4>
Terminal A2 Input
Gain
Sets the terminal A2 input gain as a percentage
when inputting 10V
Default: 100.0 %
Min.: -999.9 %
Max.: 999.9 %
E3-09
<4>
Terminal A2 Input
Voltage Bias
Sets the terminal A2 input voltage bias as a
percentage when inputting 0V.
Default: 0.0%
Min.: -999.9 %
Max.: 999.9 %
E3-10
<7>
Terminal A2
(4-20mA) lost
0 : no disconnection selection
1 : Operate according to P4-03 frequency setting
Default: 0
Range: 0 to 3