155
PD-55
LVL
The level for the error of the low voltage
Communication
address:
036EH
036FH
Initial value
160
Control mode
ALL
Unit
Volt.(rms)
Configuration range
140 ~ 190
Data size
16bit
Data format
Dec
This parameter set the low-voltage detection level. The low-voltage alarm is released when the mains supply is
lower than this setting. (After the low-voltage error is eliminated, power must be reconnected to the drive to
clear the alarm.)