5.1.2 Environment Requirements
The inverter must be installed in a ventilated environment to ensure good heat dissipation.
Make sure the installation meets the following conditions:
•Not in areas where highly flammable materials are stored.
•Not in potential explosive areas.
•Not in the cool air directly.
•Not near the television antenna or antenna cable.
•Not higher than altitude of about 2000m above sea level.
•Not in environment of precipitation or humidity (>95%).
•The ambient temperature in the range of -20℃ to +60℃.
•The slope of the wall should be within ±5°.
•The wall hanging the inverter should meet conditions below:
•The wall must be solid enough to bear the weight of the inverter.
•Do not install the inverter on a wall made of gypsum boards or similar materials with
weak sound insulation to avoid noise disturbance in a residential area.
5.1.3 Angle and Space Requirements
• Never install the inverter horizontally, or with a forward tilt or with a backward tilt
or even with upside down. The horizontal installation can result in damage to the
inverter.
• Install the inverter upright or at a maximum back tilt of 15 degrees to facilitate heat
dissipation.