Electronic Control "LCM" User Manual
firmware 0.06 Rev.02 EN 7/ 15
5.8. Plant configuration ()
(password) 1
0= 2 Pipes (unique changeover coil)
1= 2 Pipes + Heater (cooling coil + electrical post heater)
2*= 4 Pipes (cooling coil + heating coil)
3= 4 Pipes + Heater (cooling coil + heating coil + electrical post heater)
(Post heating valve enable AO3)
(Inverter fan enable)
(Air flow control) reboot the controller after setting
2=Supply and exhaust pressure, 2 Probes (500Pa)
3=Supply air pressure (500Pa)
4= PIR (occupant sensor) + Temperature
1= Dehumidification by digital input
2= Dehumidification by analog input
3= Humidification by digital input
4= Humidification by anlog input
5= Dehumidification /summer) - humidification (wintyer) by analogl input
(Mixing damper enable)
1= ON (with mixing dampers only)
2= CO2 digital sensor + ON-OFF dampers (DO1)
3= CO2 analog sensor + modulating dampers (AO3)
(Regulation probe)
1* = Display (SKW keyboard) or return air
(Room regulation probe)
0= Display (SKW keyboard AIR1)
1= Display clamps (SKW keyboard AIR2)
2*= AI5 (return air probe)
(Remote summer / winter changeover enable)
(Fire alarm managment)
0*= Off, in case of fire alarm the unit is completely stopped
1= On, in case of fire alarm the dampers are open and the fans run at max speed.
2= Available only with Fanl= yes: in case of fire alarm the dampers are open and only the return fans runs at max speed.
(Water coil antifreeze sensor enable)
(Modbus protocol address) ¹
(Modbus protocol Baudrate) ¹
(Modbus protocol parity) ¹
(Alarm history reset)
* Default value
¹ To apply the changes protocol reboot the controller