7 Alarms
7.1. Fire alarm
Fire alarm can be managed in the following ways:
in case of alarm completely stop the unit.
in case of alarm open the external dampers and force max fan speed (on both fans)
Available only if  = yes: in case of alarm open the external damper and force max fan speed only for the
exhaust fan.
7.2. Stopping alarms
This kind of alarms forces the unit in stand-by mode.
These alarms are: Expansion communication error, fan thermal protection, regulation sensor fault and supply sensor
fault.
7.3. Alarm list
To visualize the alarms press Set and pressing the arrows select the  menu.
Pressing the arrows it is possible the visualize more than one alarm
To reset manual alarms, keep pressed Set button while visualizing the alarm code.
Alarm code
Description
Solution
Reset
฀
Supply Air Probe Error
Check / Replace the sensor
Auto
฀
Fresh Air Probe Error
Check / Replace the sensor
Auto
฀
Remote Display Probe Error
Check the connection / Replace remote Display
Auto
฀
Filter Alarm
Clean or replace the filters
Auto
฀
Post-Heater Overheating Alarm
Check the unit air flow rate / Contact the service centre
Manual
฀
Return Air Pressure Probe Error
Check the connection / Replace the sensor
Auto
฀
Supply Air Pressure Probe Error
Check the connection / Replace the sensor
Auto
฀
CO
2
Probe Error
Check the connection / Replace the sensor
Auto
฀
Fan Thermal Protection Alarm
Check the unit air flow rate / Contact the service centre
Manual
฀
Antifreeze Probe Error
Check / Replace the sensor
Auto
฀
Pre-Heater Overheating Alarm
Check the unit air flow rate / Contact the service centre
Manual
฀
Expansion Communication Alarm
Check the connection / Contact the service centre
Auto
฀
Antifreeze Alarm
Check the hot water temperature and the pump
Auto
฀
Fire Alarm
-
Manual
฀
Low Water Temperature Alarm
Check the hot water temperature and the pump
Auto
฀
Clock time alarm (broken or not powered for three days)
Set the clock
Manual or setting the clock
฀
Remote Display Probe AIR2 Error
Check / Replace the sensor
Auto
฀
Return Air Probe Error
Check / Replace the sensor
Auto