EasyManua.ls Logo

LOYTEC L-STAT - Page 39

LOYTEC L-STAT
61 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L-STAT User Manual 39 LOYTEC
Version 1.0 LOYTEC electronics GmbH
Description
Register
Address
Bit Position
283
0x011B
VSA
[0]
VEU
[0]
DSSA
[0]
DSEU
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
config_display_
value_14
284
0x011C
unit_modbus
[0x0]
unit_lstat
[0x0]
CAL
[0]
semantic_meaning
[0x00]
285
0x011D
VSA
[0]
VEU
[0]
DSSA
[0]
DSEU
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
config_display_
value_15
286
0x011E
unit_modbus
[0x0]
unit_lstat
[0x0]
CAL
[0]
semantic_meaning
[0x00]
287
0x011F
VSA
[0]
VEU
[0]
DSSA
[0]
DSEU
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
[0]
These registers hold the configuration of the 16 display values.
For both, unit_lstat and unit_modbus the following values are possible:
0x0
0x1
0x2
0x3
0x4
0x5
0x6
0x7
0x8
0x9
0xA
0xB
no
unit
°C
°F
cfm
l/s
m³/h
Pa
inWC
V
%
%RH
ppm
Bits 0-11 of the higher address of each configuration register indicate the symbols that are
displayed along with the corresponding display value.
These two bits define if the value displayed is taken from a display_value register at address
64 to 79 (see Table 11 on Page 25) or from a sensor_value register at address 48 to 56 (see
Table 10 on Page 24). The following states are valid:
0 defines that the value is taken from a display_value register that has to be set via
modbus
1 defines that the value is taken from a sensor_value (+ offset_value) register that is
automatically updated with the current sensor value
VEU:
visible for end user
VSA:
Visible for system administrator
These two bits define if the display value is visible for the end user and/or the system
administrator. If set to 1 the value will be visible.
See Table 31 on Page 43 for example configurations of display values or set points.
* Please note that config_display_value_3 register is only configured as above per default
for LSTAT-802-Gx-Lx devices for displaying the actual CO
2
level. Otherwise all bits of
this register are set to 0’.
semantic_meaning:
is used to provide information about the semantic meaning and the
source of the value. For further information please see Table 30 on
Page 42.
CAL:
if set to 1 the corresponding offset_value can be edited in
CALIBRATION-mode (only capable if DSEU or DSSA is set to
1’)
unit_lstat:
defines a unit with which the corresponding display value appears
on the LCD
unit_modbus:
defines a unit that the corresponding display value register appeare
on Modbus
DSEU:
display source for end user
DSSA:
diplay source for system administrator
Table 28: Display Value Configuration