46
;AD7!===IgYfAUbiU`
Setting Data
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Fault #1
Ir>
(1)
Is>
(1)
It>
(1)
In>
(1)
Ir>>
(1)
Is>>
(1)
It>>
(1)
In>>
(1)
Fault #2
OVR
(1)
UVR
(1)
VG>
(1)
SGR
(1)
VG>>
(1)
(1) 0
Sys.
(1)
CB
Local
ON
(0)
Local
OFF
(0)
Remote
ON
(0)
Remote
OFF
(0)
0 0
ON
(1)
OFF
(0)
Setting /
Reset
Relay
Setting
(0)
Fault
Reset
(0)
V0 Max
(0)
CB ON
Time
(0)
CB ON
Counter
(0)
SOE
Buffer
(0)
Varh
(0)
Wh
(0)
* ‘1’; Enable, ‘0’; Disable.
* The value between the brackets is a default.
11.3 Command for controlling CB on/off
To control CB on/off on remote, it transmits the command for selecting control point and
for operating control point sequentially.
11.3.1 SBO (Select Before Operate)
It applies to command for CB Open/Close.
Transmitting the command for selecting control point to GIPAM.
GIPAM replies with ACK Signal.
Transmitting the command for operating the point selected before
time’s up.
GIPAM replies with ACK Signal as well as outputs the control
signal.
11.3.2 Reacting to other command after receiving the command for
selecting control point.
Disregarding a command to control other CB.
Canceling the selected point to control CB in the event of receiving the
command to control other one.
Canceling the selected point if there is something wrong with the
command.
Responding to a command that requests Measurement data normally.