5-1 Set the CT/PT ratio.
According to the CT/PT ratio, you can set the Dip switch by referring the following table.
The WH/VARH Pulse output is decided by the ratio of the CT/PT ratio.
Bit setting Bit setting
Dip S/W #1
1 2 3 4 5 6 7 8
Dip S/W #2
1 2 3 4 5 6 7
8
110 : 110V 0 0 0 0 5 : 5A 0 0 0 0 0
220 : 110V 0 0 0 1 10 : 5A 0 0 0 0 1
380 : 110V 0 0 1 0 15 : 5A 0 0 0 1 0
440 : 110V 0 0 1 1 20 : 5A 0 0 0 1 1
3300 : 110V 0 1 0 0 25 : 5A 0 0 1 0 0
6600 : 110V 0 1 0 1 30 : 5A 0 0 1 0 1
11000 : 110V 0 1 1 0 40 : 5A 0 0 1 1 0
13200 : 110V 0 1 1 1 50 : 5A 0 0 1 1 1
13800 : 110V 1 0 0 0 60 : 5A 0 1 0 0 0
22000 : 110V 1 0 0 1 75 : 5A 0 1 0 0 1
22900 : 110V 1 0 1 0 80 : 5A 0 1 0 1 0
33000 : 110V 1 0 1 1 100 : 5A 0 1 0 1 1
66000 : 110V 1 1 0 0 120 : 5A 0 1 1 0 0
1P2W Connection 0 0 150 : 5A 0 1 1 0 1
1P3W Connection 0 1 200 : 5A 0 1 1 1 0
3P3W Connection 1 0 250 : 5A 0 1 1 1 1
3P4W Connection 1 1
300 : 5A 1 0 0 0 0
400 : 5A 1 0 0 0 1
500 : 5A 1 0 0 1 0
600 : 5A 1 0 0 1 1
750 : 5A 1 0 1 0 0
800 : 5A 1 0 1 0 1
1000 : 5A 1 0 1 1 0
1200 : 5A 1 0 1 1 1
1500 : 5A 1 1 0 0 0
2000 : 5A 1 1 0 0 1
2500 : 5A 1 1 0 1 0
3000 : 5A 1 1 0 1 1
4000 : 5A 1 1 1 0 0
5000 : 5A 1 1 1 0 1
6000 : 5A 1 1 1 1 0
On 1
Battery
Back-up
Off 0
After installation
‘ON’
Impossible 0
Calibration
Possible 1