12
GIPAM User Manual
6-1-6. Display for the system error
Error code will be displayed in case of it is out of order. Error code is displayed as
followings :
Error 0: PT ratio setting is wrong.
Error 1: CT ratio setting is wrong.
Error 2: Detect voltage error of analog circuit and input circuit.
Error 3: Detect internal telecommunication error.
Error 4: Detect CPU abnormal operation.
6-2 Protection part
6-2-1 Initialization setting
1) DIP switch setting
Set up a use frequency and an assigned function of relay.
2) Calibration of input amount of energy
Please do not adjust a calibration mode temporarily. If there are
necessity of adjustment, please refer to appendix.)
6-2-2. Operation
1) Display of operating status
- After power is on, DOT-matrix and LCD part will be turned on during
1 second. If displayed [Run], it means normal operating status.
- It displays system error and fault of relay.
- Function of each key
[SET/RUN] : Changing the normal mode to the setting mode or vise versa.
[CHAR] : It is an effective key at setting mode and makes possible to move
among the setting menu of each really facts.
[] : It is effective key at setting mode and it makes possible to decrease the
set data.
[] : It is effective key at setting mode and it makes possible to increase the
set data.
[ENT] : It is effective key at setting mode and it saves the corrected data.
[RESET] : It is effective key at Normal mode When remove the
cause of system error and fault, it resets error indication.