11
GIPAM User Manual
4) FUNC+W: It displays a settled own address at telecommunication part of main board.
5) FUNC+Var: It displays the number of operation time of the circuit breaker
which is connected to CB ON input contact.
6) FUNC+PF: It displays all the measured data by the following sequence in a
row(V → A → W → VAR → WH → VARH → F → PF, Voltage/Current: every
phases have been measured.)
7) FUNC+Wh: It displays the let through time(Hour unit) of the CB which is connected
to the CB ON input contact. When the time is over 9999hours, it displays the time
by the bargraph on the 10000 hours unit.
8) FUNC+VARH: It displays Vo with N1 and Vo max. with N2.
6-1-4. CB operation and local or remote control
1) LOCAL: It is the key for the local operation . If press this button, local output
contact will be on and it makes possible to operate C/B on or off by pressing the
keys on the front.
2) Remote: It is the key for the remote control . If press this button, remote output
contact will be on and it can be possible to operate C/B on or off by
telecommunication at host computer.
3) CB ON/OFF: If press the ON/OFF switch, output contact will be conducted during
from 0.5 to 0.6 seconds. It makes operate CB(ON/OFF Operation) when local
operation switch is selected.
6-1-5. Others
1) Clear switch
. The clear switch in the back plate reset the WH & VARH value to “0”
. The users should press the reset button when you first install the system.
2) CPU Reset button
. The CPU reset switch in the back plate clear all the data in the CPU. When you
found the operations of the equipment is unusual, you can press and restart.
3) COMM LED
During the communication with monitoring computer, it is go on and off.