are swapped and transmitted on GMPC III MODBUS communication.
For example when GMPC III receives the data which is a type of Floating point as below
from other devices such as GIMAC II, GIPAM, and so forth.
" 01h 02h 03h 04h "
It transmits the data changed as follow to the master station.
" 03h 04h 01h 02h "
12.3 USABLE ADDRESS RANGE in each Device
Device
NAME
COIL CONTACT
INPUT
REGISTER
HOLDIG REGISTER
GIMAC-II 41 ~ 101 Unused 30001 ~ 30105 40001~43341
u-RTU Unused Unused 31001 ~ 31024 41001 ~ 41101
u-RTU II Unused Unused 31501 ~ 31545 41501 ~ 41641
GIMAX III 2001 ~ 2141 Unused 32001 ~ 32246 42001 ~ 42025
GIPAM 3041 ~ 3381 Unused 33001 ~ 33321 43001 ~ 43361
DPR 4001 ~ 5000 Unused 34001 ~ 36647 44001 ~ 44106
GMPC III 39900 49900
12.4 Usable MODBUS OPCODE
OP CODE READ/WRITE Description
04h READ INPUT REGISTER
05h WRITE COIL
06h WRITE HOLDIG REGISTER(u-RTU)
10h WRITE HOLDIG REGISTER
12.5 ADDRESS Setting in each Device
12.5.1 GIMAC-II
OP CODE Description DATA TYPE ADDRESS Description
Status Data QUERY
04h DEVICE ID BYTE 30001
* Lower 1 BYTE
04h Fault Status Data INT 30002
BIT Operation
Example) 30002 :8