EasyManua.ls Logo

LS Industrial Systems GIPAM - Page 107

LS Industrial Systems GIPAM
123 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
;AD7!===IgYfAUbiU`
OP CODE Description DATA TYPE ADDRESS Description
0 – Bit7 : Heavy Fault Output
(Previous Status)
1 Bit6 : Light Fault Output
(Previous
Status)
2 Bit5 : OVGR Fault Input
(Previous
Status)
3 Bit4 : OCGR Fault Input
(Previous
Status)
4 – Bit3 : OVR Fault Input
(Previous Status)
5 – Bit2 : UVR Fault Input(Previous Status)
6 – Bit1 : SGR Fault Input(Previous Status)
7 – Bit0 : OCR Fault Input(Previous Status)
8 – Bit7 : Heavy Fault Output(Current Status)
9 – Bit6 : Light Fault Output
(Current Status)
10 – Bit5 : OVGR Fault Input
(Current Status)
11 – Bit4 : OCGR Fault Input(Current Status)
12 – Bit3 : OVR Fault Input
(Current Status)
13 – Bit2 : UVR Fault Input
(Current Status)
14 – Bit1 : SGR Fault Input
(Current Status)
15 – Bit0 : OCR Fault Input
(Current Status)
04h
CB,RESET Status
Data
INT 30003
BIT Operation
Example) 30003:8
0,1,2 – Bit7,6,5 : Reserved
3 – Bit4 : CB ON Output Status
4. – Bit3 : CB OFF Output Status
5 – Bit2 : 0 = LOCAL, 1=REMOTE
6 – Bit1 : CB ON Input Status
7 – Bit0 : CB OFF Input Status
8 – Bit7,6,5,4 : Reserved
9 – Bit3 : REMOTE FAULT RESET
10 – Bit2 : LOCAL FAULT RESET
11 – Bit1 : REMOTE WH RESET
12 – Bit0 : LOCAL WH RESET
04h 3 Phase Current
IR FLOAT 30021 Example) 30021 F
IS FLOAT 30023 Example) 30023 F
IT FLOAT 30025 Example) 30025 F
04h Line-To-Line Voltage
VRS FLOAT 30041 Example) 30041 F
VST FLOAT 30043 Example) 30043 F
VRT FLOAT 30045 Example) 30045 F
04h
Power Factor, Active
Power, Reactive
Power
PF FLOAT 30061 Example) 30061 F
W FLOAT 30063 Example) 30063 F
VAR FLOAT 30065 Example) 30065 F
04h
Frequency, Active
Energy, Reactive Energy
FREQ FLOAT 30081 Example) 30081 F
WH FLOAT 30083 Example) 30083 F
VARH FLOAT 30085 Example) 30085 F
04h Phase Voltage

Table of Contents