51
;AD7!===IgYfAUbiU`
OP CODE Description DATA TYPE ADDRESS Description
0 – Bit7 : Heavy Fault Output
(Previous Status)
1 – Bit6 : Light Fault Output
(Previous
Status)
2 – Bit5 : OVGR Fault Input
(Previous
Status)
3 – Bit4 : OCGR Fault Input
(Previous
Status)
4 – Bit3 : OVR Fault Input
(Previous Status)
5 – Bit2 : UVR Fault Input(Previous Status)
6 – Bit1 : SGR Fault Input(Previous Status)
7 – Bit0 : OCR Fault Input(Previous Status)
8 – Bit7 : Heavy Fault Output(Current Status)
9 – Bit6 : Light Fault Output
(Current Status)
10 – Bit5 : OVGR Fault Input
(Current Status)
11 – Bit4 : OCGR Fault Input(Current Status)
12 – Bit3 : OVR Fault Input
(Current Status)
13 – Bit2 : UVR Fault Input
(Current Status)
14 – Bit1 : SGR Fault Input
(Current Status)
15 – Bit0 : OCR Fault Input
(Current Status)
04h
CB,RESET Status
Data
INT 30003
BIT Operation
Example) 30003:8
0,1,2 – Bit7,6,5 : Reserved
3 – Bit4 : CB ON Output Status
4. – Bit3 : CB OFF Output Status
5 – Bit2 : 0 = LOCAL, 1=REMOTE
6 – Bit1 : CB ON Input Status
7 – Bit0 : CB OFF Input Status
8 – Bit7,6,5,4 : Reserved
9 – Bit3 : REMOTE FAULT RESET
10 – Bit2 : LOCAL FAULT RESET
11 – Bit1 : REMOTE WH RESET
12 – Bit0 : LOCAL WH RESET
04h 3 Phase Current
IR FLOAT 30021 Example) 30021 F
IS FLOAT 30023 Example) 30023 F
IT FLOAT 30025 Example) 30025 F
04h Line-To-Line Voltage
VRS FLOAT 30041 Example) 30041 F
VST FLOAT 30043 Example) 30043 F
VRT FLOAT 30045 Example) 30045 F
04h
Power Factor, Active
Power, Reactive
Power
PF FLOAT 30061 Example) 30061 F
W FLOAT 30063 Example) 30063 F
VAR FLOAT 30065 Example) 30065 F
04h
Frequency, Active
Energy, Reactive Energy
FREQ FLOAT 30081 Example) 30081 F
WH FLOAT 30083 Example) 30083 F
VARH FLOAT 30085 Example) 30085 F
04h Phase Voltage