28
GIPAM User Manual
7. Installing & Operating Device
7-1. How to install
1) Set CT/PT Ratio, Wiring and select relays with DIP Switches located on the Main Board
of the device.
2) Set an Address Number with the Address Knob which is deeply inside of the Main Board.
3) Supply the power (DC 110V).
4) Input the Voltage and Current.
5) By pressing the CLEAR S/W on the front, reset CB Operation, CB ON Time etc.
7-2. Set the DIP Switches.
Drawing out the device after taking off the screws on the front, there are four of the DIP
Switches on top of the Main Board as below.