30
GIPAM User Manual
7-3. Setting a Communication Address Number
It is set by the two knobs on top of the Main Board and each knobs has hexa-decimal scale
marks from ‘0’ to ‘F'.
Using these two knobs, it is possible to set 255 Address Numbers from '01' up to ‘FF'. For
example, if '0' is set on the first(left) knob and '1' is set on the second(right) knob,
then Communication
Address of this Device becomes '01'.
7-4. Check the Configuration of device (See 6-1-3.Special Function)
It is possible to check out the configuration data with using FUNC Key among the
Measurement Keys on the front. When the LED of FUNC Key is on, you can easily
check out the data by pressing V, A, F, or W Key.
1) PT Ratio
Pressing V key when the LED of FUNC Key is on, PT Ratio is displayed on the LCD.
2) CT Ratio
Pressing A key when the LED of FUNC Key is on, CT Ratio is displayed on the LCD.
3) Wiring
Pressing F key when LED of the FUNC Key is on, Wiring is displayed on the LCD.
4) Communication Address
Pressing F key when LED of the FUNC Key is on, Address Number is displayed on the LCD.
7-5. The Connection with the main line.
It differs with applied wiring systems and is connected as follows.
1) Sigle-Phase Two-Wire System
B09(VR+)
B10(VR-)
B01(IR+)
B02(IR-)