GIPAM User Manual
5 Spacification
5-1 Metering
1)Input specification
Contents Rating
Wiring Type 1P2W, 1P3W, 3P3W, 3P4W
Frequency 60Hz
Voltage AC10~132V/AC20~264V
Input
Range
Current 0.2~6A
2) Range of the metering result
Meter Menu Metering Value Displayed Range Accuracy(%) Remarks
Voltage(V) RMS Value LCD: AC10~154000(V)
Bargraph:0 to 120(%)
± 1.0%
Between Phases
Between phase and
Neutral
Current(A) RMS Value
LCD: AC0.2~6000(A)
Bargraph:0 to 120(%)
± 1.0%
Each phase
Zero Phase Voltage(Vo) RMS Value 0~190(V) ± 2.5%
Max. Value back up
Active, Watt Average Value LCD: 0~9999(MW)
Bargraph:0 to 120(%)
± 2.0% Power
Reactive,
Vars
Average Value LCD: 0~9999(MVars)
Bargraph:0 to 120(%)
± 2.0%
Active, Wh Accumulated Value 0-999999(MWh) ± 2.0% Energy
Reactive, Varh Accumulated Value 0-999999(MVarh) ± 2.0%
Power Factor, PF Average Value Lead/Lag 0-100(%) ± 2.0%
Frequency(Hz) Average Value 45~65(Hz) ± 0.5%
3) Input/Output Contact
MENU Contents Type Rating
Input
CB-ON
CB-OFF
DC110(V) Connected Voltage and Current to origin of signal:
DC110V, 5mA Max
OCR
OCGR
OVR
UVR
OVR
SGR
Alarm
System Error
CB-ON
CB-OFF
Zero Voltage
"a" Contact
Output
REM/LOC "C" Contact
Resitance Load: AC250V, 10A
DC 30V, 10A CosΦ=1.0
Induction Load: AC250V, 7.5A
DC 30V, 5A
CosΦ=0.4, L/R=7ms
Switching Capacity: 2.500VA, 300W