23
;AD7!===IgYfAUbiU`
If there is an error on the data that GMPC received, GMPC requests restarting SYNC
SEQUENCE via transmitting REQUEST_RESTART_SYNC frame to the Host system.
Since the Host system receives REQUEST_RESTART_SYNC frame from GMPC, it restarts
SYNC SEQUENCE as requested.
If there is an error on the data that the Host system received, the Host system restarts
SYNC SEQUENCE via transmitting SYNC_PRECI_SYNC frame to GMPC.
START_PRECI_SYNC
PC GMPC-III 0xFF + 0x00 + 0x?? + 0x21 + 0x01 + ECC
[DATA-0] 0x01 START_PRECI_SYNC
REQUEST_ADJUST
PC GMPC-III 0xFF + 0x00 + 0x?? + 0x21 + 0x01 + ECC
[DATA-0] 0x01 REQUEST_ADJUST
TIME_ADJUST
PC GMPC-III
0xFF + 0x00 + 0x?? + 0x2C + 0x02 + year + mon + day +
A2(4) + A1(4) + ECC
[DATA-0]
[DATA-1]
[DATA-2]
[DATA-3]
[DATA-4 - 7]
[DATA-8 – 11]
0x02
year
mon
day
A2
A1
Time_Adjust
Inputting the last two digits of year as binary
Inputting the value of month as binary
Inputting the value of date as binary
Inputting the value of millisecond(Long Word, 4-Byte)
Inputting the value of millisecond(Long Word, 4-Byte)
END_PRECI_SYNC
PC GMPC-III 0xFF + 0x00 + 0x?? + 0x21 + 0x02 + ECC
[DATA-0] 0x02 END_PRECI_SYNC