Chapter 6 Usage of Various Functions
6-19
(2) PID8AT
Available device Flag
Instruction
M P K L F T C S D
#
D
inte
ger
No. of
Steps
Error
(F110)
Zero
(F111)
Carry
(F112)
n
O
O
PID8AT
S1
O
5 O
■ PID8AT (Auto-tuning by parameter)
a) Usage
• When the condition of execution is on, PID auto tuning operation executes and calculates
P,I,D constant.
• ‘n’ is registration No.at parameter( 0 ~ 7)
• S1 is execution status and P,I,D constant registration area.
b) Example program
• When the input condition M0 turns on, PID operation executes at no.2 parameter.
• PID execution status stores D0000 and the output value of control result stores D0001
and P,I,D constant sequentially store D002(P),D003(I),D004(D).
PID8AT n S1
Flag Set
Error
(F110)
Error flag turns on when designating
area is over and the instruction isn’t
executed.
Desi
nation
n
Re
istration No. at
arameter
0~7
S1
Execution status re
istration area
Done : normal execution signal
D0000
Auto tuning end bit
b0b6b7bF bE bD bC bB bA b9 b8 b1b2b5 b4 b3