EasyManua.ls Logo

LSIS LSLV-G100 - Page 271

LSIS LSLV-G100
343 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Code
Comm.
Address
Name
Setting Range
Initial
Value
Property*
V/F
SL
Ref.
acceleration.
0010
Initialization
after a fault trip
0100
Restart after
instantaneous
power
interruption
1000
Starting with
power-on
Cn-72
25
0h1448
Speed search
reference
current
80200 (%)
150
O
O
O
p.145
Cn-73
26
0h1449
Speed search
proportional
gain
09999
Flying
Start-1
: 100
O
O
O
p.145
Flying
Start-2
: 600
27
Cn-74
26
0h144A
Speed search
integral gain
09999
Flying
Start-1
: 200
O
O
O
p.145
Flying
Start-2
: 1000
Cn-75
26
0h144B
Output block
time before
speed search
0.060.0 (s)
1.0
X
O
O
p.145
Cn-76
26
0h144C
Speed search
Estimator gain
50150 (%)
100
O
O
O
-
Cn-77
0h144D
Energy
buffering
selection
0
No
0: No
X
O
O
p.140
1
KEB-1
2
KEB-2
Cn-78
28
0h144E
Energy
buffering start
level
110.0200.0 (%)
125.0
X
O
O
p.140
Cn-79
28
0h144F
Energy
Cn78210.0 (%)
130.0
X
O
O
p.140
25
26
27
28

Table of Contents