Chapter 2 System configuration MASTER-K
2-11
2.3 System configuration types
System configuration is classified into 3 types such as basic, computer link, and network system.
2.3.1 Basic system configuration
The basic system consists of a main base and expansion base(s). The main and expansion
base(s) are connected via expansion cable.
K200S K300S K1000S
Max. expansion level 3 levels
Max. distance between bases 3 m
Max. numbers of I/O module 12 modules 32 modules
Max. I/O points 384 points 512/1,024 points
1
1,024 points
CPU K3P-07AS K4P-15AS K7P-30AS
Power supply
GM6-PAFA/B/C
GM6-PDFA/B
GM4-PA1A/PA2A
GM4-PA1B/PA2B
GM4-PD3A
GM3-PA1A/PA2A
GM3-PA1B/PA2B
GM3-PD3A
Main base
GM6-
B04/06/08/12M
GM4-
B04/06/08/12M
GM3-B04/06/08M
Expansion base GM4-B04/06/08E GM3-B04/06/08E
Expansion cable G4C-E041/121/301 G3C-E061/121/301
Module
type
I/O module
Special-function
module
G6I-
G6Q-
G6F-
G4I-
G4Q-
G4F-
G3I-
G3Q-
G3F-
I/O number allocation
I/O number (P00, P01, …) is allocated for each module
automatically. A empty slot occupies 16 bits.
Special-function modules can be mounted on all bases and
slots with no limit on the number of modules.
1
Only in 3.0 or higher CPU O/S version
Power
Main base
Expansion
base
Expansion
cable
CPU
Slot 0
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7
Power
Slot 0
Slot 1
Slot 2
Slot 3
Slot 4
Slot 5
Slot 6
Slot 7