13.8 Error code list
The following table shows the error code list that PLC returns when NAK error occurs.
Error
code
Error type Description Corrective action
h0001 PLC system error It is unable to interface with PLC Cycle the power of PLC
h0011 Data error
It is unable to convert ASCII
codes to numeric data
Make sure that there is no
characters other than
alphabet, number, and %
in device definition and
data
h0021 Instruction error Wrong instruction
Check instruction if other
character is used than R(r),
W(w), S(s), X(s), and Y(y).
h0031
Instruction type
error
Wrong instruction type Revise instruction type
h1132
Device memory
error
Wrong device memory
assignment
Use correct device (P, M, L,
K, T, C, F, S, or D)
h1232 Data length error
The length of data is 0 or exceeds
120 bytes (60 words)
Correct the length of data
h2432 Data type error Wrong data type Use bit or word data type
h7132
Device definition
format error
Missing % at the first of data
definition
Correct the data definition
format
h2232 Range over error
The data definition (P, M, L, K, T,
C, F, S, or D) is out of its range
Correct the data definition
not to exceed its range
h0190
Monitor execution
error
The assigned monitor registration
number is not exist or over the
range (0 ~ 9)
Correct the monitor
registration number
h0290
Monitor registration
error
The registration number is out of
range (0 ~ 9)
Correct the registration
number
h6001 Syntax error
Device definition error
Ex1) Wrong data type such as
%DX or %SX (D and S area can
be accessed with WORD type)
Ex2) Wrong address definition
such as %px0 (address definition
should be 2 ~ 8 digit)
Ex3) Try to write on F area (F area
is read-only memory)
Correct the device
definition format
h6010 Syntax error Over-run or frame error Cycle the power of PLC
h6020 Syntax error Time-out error
Check the configuration of
RS-232C port of external
device
Cycle the power of PLC
h6030 Syntax error Wrong request frame
Check the request frame
has ENQ and EOT