Chapter 2 System configuration MASTER-K
2-13
2.3.3 Network system
In network system, user can access and control I/O module of remote station through a
network I/F and remote I/F module. MASTER-K series uses the Fnet system to consist a
network system.
Besides, in 3.0 or higher CPU O/S version and in 3.2 or higher KGL-WIN version, user who want
to use other network system can use the Dnet I/F system or
Profibus I/F to construct a network
system. (Dnet I/F system or
Profibus I/F system is available for K300S and Profibus I/F system is
available for K1000S)
Please refer the user’s manual of Fnet network module for details.
Remark
1. Fnet network module can be mounted on main a base board only. It can not be mounted on a
expansion base board
The maximum number of Fnet modules that can be mounted simultaneously is as following;
K300S: 2 modules K1000S : 4 modules
2. In 3.0 or higher K300S/1000S CPU O/S version , high-speed link communication module can
be mounted on a main or expansion base board and the maximum number that can be
mounted simultaneously is 4
3. The remote system has same configuration with a basic system configuration. However, the
following modules can not be used on the remote system which a Fnet remote I/F module is
mounted.
PID control module G4F-PIDA G3F-PIDA
Positioning module G4F-POPA G3F-POPA
G4F-POPB G3F-POAA
Analog timer module G4F-AT3A G3F-AT4A
Fnet I/F module G4L-FUEA G3L-FUEA
Cnet I/F module G4L-CUEA G3L-CUEA
Example) K300S Network system
GM4-PA2A
K4P-15AS
G4L-FUEA
GM4-PA1A
K4F-RBEA
Fnet I/F module
Main base
Fnet remote
I/F module
The above modules can not
be mounted on these slots