7.3.2 16 points relay output module
K200S K300S K1000S Type
Item
G3Q-RY2A G4Q-RY2A G3Q-RY2A
Output points 16 points
Insulation method Photo coupler
Per 1 point
24 VDC / 2A (resistive load), 220 VAC / 2A (cosψ = 1)
Rated load
voltage / current
Per 1 COM 5A / 1COM 4A / 1COM 8A / 1COM
Minimum load voltage/current 5 VDC / 1mA
Maximum load voltage 110 VDC / 250 VAC 125 VDC / 250 VAC
Leakage current 0.1 mA ( 220 VAC, 60Hz )
Maximum switching frequency 1,200 times / hour 3,600 times / hour
Surge absorber None
Mechanical No load Over 20 million times
Rated voltage / current Over 0.1 million times
200VAC / 1.5A, 240VAC / 1A (cosψ = 0.7)
Over 0.1 million times
200VAC / 1A, 240VAC / 0.5A (cosψ = 0.35)
Over 0.1 million times
Lifetime of
contact
Electrical
24VDC / 1A, 100VDC / 0.1A (L / R = 7ms) Over 0.1 million times
Off Æ On 10 msec or less
Response time
On Æ Off 12 msec or less
Common method 8 point / 1COM
Internal current consumption 400mA (all outputs on) 100mA (when all outputs are on)
Voltage None
24 VDC ± 10% ( ripple : 4 Vp-p or less )
External power
supply
Current None Max. 100mA Max. 150 mA
Operation indicator LED
External wiring
18 points terminal block
connector
20 points terminal block connector
Weight 190 g 310 g 460 g
Wiring diagram
[ G6Q-RY2A ] [ G4Q-RY2A ] [ G3Q-RY2A ]
00
L
01
02
03
04
05
06
07
08
L
09
0
A
0B
0C
0D
0E
0F
5
7
9
11
13
15
17
19
1
3
6
8
10
12
14
16
18
20
2
4
N.C
N.C
00
L
01
02
03
04
05
06
07
08
L
09
0
A
0B
0C
0D
0E
0F
8
9
10
1
2
17
18
19
11
20
N.C
N.C
0
1
7
COM1
L
L
L
8
9
F
COM2
L
L
L

Table of Contents

Related product manuals