Chapter 8 Power supply modules MASTER-K
8-1
8 Power supply modules
In this chapter, it will be described that the power supply modules of MASTER-K series.
8.1 Selection of power supply module
When select a power supply module of PLC system, it should be considered that the total
current consumption of CPU module, digital I/O modules, special purpose modules, and
communication modules. If the power capacity of power supply module is smaller than the total
current consumption of PLC system, it may cause a malfunction on operation. The following
table shows a current consumption of MASTER-K 200S/300S/1000S series.
8.1.1 K200S
(unit : mA)
Module Catalog No.
Current
consumption
Module Catalog No.
Current
consumption
K3P-07AS 170 A/D conversion G6F-AD2A 50
K3P-07BS 210 G6F-DV2A 50
CPU
K3P-07CS 170
D/A conversion
G6F-DI2A 50
G6I-D21A 40 High speed counter G6F-HSCA 220
G6I-D22A 70 Positioning G6F-POPA 345
G6I-D22B 70 Cnet link G6L-CU2A 140
G6I-D24A 75 G6L-CU4A 180
12/24VDC input
G6I-D24B 75 Fnet I/F G6L-FUEA 215
110VAC input G6I-A11A 41 Fnet remote I/F G6L-RBEA 215
220VAC input G6I-D21A 41
G6Q-RY1A 210
Relay output
G6Q-RY2A 400
G6Q-TR2A 180
G6Q-TR2B 170
G6Q-TR4A 140
Transistor output
G6Q-TR4B 145
Triac output G6Q-SS1A 190
12/24VDC input
+ Relay output
G6H-DR2A 270

Table of Contents