Page #22 background image
Lucent Technologies Lineage
®
2000 ECS Battery Plant J85500D-3
2 - 4 Product Description Issue 5 January 1999
ECS battery
plant physical
description
The Lineage
®
2000 Evolutionary Control System (ECS) Battery
Plant is shown in Figure 1-1. The ECS battery plant provides
power for the using equipment as well as float and recharge
capability for the battery reserve. The plant operates from a
nominal 208/240 Vac, 50/60 Hz source. It offers a 300-ampere
total plant capacity with a nominal -48 Vdc output. The ECS
battery plant can be mounted on a battery stand which provides
space for one 48-volt string of VR Series batteries or on a battery
stand which provides space for four 48-volt strings of 12IR125
batteries. The ECS plant is capable of operating in a batteryless
mode, making it suitable for those applications where battery
backup is not necessary or is provided by an uninterruptible
power supply (UPS).
The ECS battery plant uses state-of-the-art technology to
achieve dramatic equipment size and weight reduction and to
minimize maintenance. These advantages are realized by the
application of Switch-Mode Rectifier (SR) and Valve-Regulated
(VR) battery technologies and a unique plug-in rectifier and
circuit breaker design.
The ECS battery plant is designed as a totally integrated energy
system package. It is a compact and complete system containing
a controller, rectifiers, circuit breaker distribution panel and
optional automatic battery disconnect/reconnect (LVD/R)
feature, optional low voltage load disconnect feature, batteries,
and optional thermal slope/step compensation feature. The plant
is a modular front-access design for ease of installation, growth
and maintenance. This power system is ideal for use in confined
areas and enables one to utilize valuable floor space in a more
efficient manner.
Initial bay
The initial bay will accommodate a maximum of six Lineage
®
2000 SR Series 50 ampere rectifiers, a Lineage
®
2000 ECS
controller, a distribution panel capable of accepting a maximum
of 42 circuit breakers/fuses of 3 to 50 ampere capacity, or 20
circuit breakers of 60 to 100 ampere capacity, a low voltage
battery disconnect/reconnect feature, low voltage load
disconnect feature and one 48-volt string of Lineage
®
2000 VR
Series, 250- or 375-ampere hour batteries, or four 48-volt strings
of Lineage
®
2000 125-ampere hour IR Series batteries.
Supplementary
bays
If additional battery reserve is required, supplementary bays are
available which can each house up to two 48-volt strings of

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lucent Technologies LINEAGE 2000 ECS and is the answer not in the manual?

Lucent Technologies LINEAGE 2000 ECS Specifications

General IconGeneral
BrandLucent Technologies
ModelLINEAGE 2000 ECS
CategoryIndustrial Electrical
LanguageEnglish

Related product manuals