Lucent Technologies Lineage
®
2000 ECS Battery Plant J85500D-3
Issue 5 January 1999 Engineering, Planning and Ordering 3 - 23
6 30 406746362 KS23616 L25
7 45 406746370 KS23616 L26
8 60 406746388 KS23616 L27
Total of 42 positions available. The 45 and 60 ampere breakers occupy two
positions and are recommended only for bottom rows (even positions from 2 to 20,
odd positions from 23 to 41.) Balance load evenly between upper and lower sides. If
cables larger than 8 gauge are required, order terminal adapter bus kit 846561447. If
8 gauge cable is required for a single position circuit breaker, order lug kit
846746857.
List 3 through 6 Fuse Options
9 -- 406980797 Fuse Holder
10 5 407006329 Fuse, TPA-5
11 10 407006337 Fuse, TPA-10
12 15 407006345 Fuse, TPA-15
13 20 407006352 Fuse, TPA-20
14 25 407006360 Fuse, TPA-25
15 30 407006378 Fuse, TPA-30
Lists 23 through 26 Circuit Breaker Options
1 3 407098417 KS23616 L31
2 5 407098425 KS23616 L32
3 10 407098433 KS23616 L33
4 15 407098458 KS23616 L34
5 20 407098474 KS23616 L36
6 25 407098482 KS23616 L37
7 30 407098490 KS23616 L38
8 40 407098448 KS23616 L48
10 45 407098516 KS23616 L40
11 50 407098524 KS23616 L41
12 *60 407098532 KS23616 L42
13 *70 407098540 KS23616 L43
14 *80 407098557 KS23616 L44
15 *90 407098565 KS23616 L45
16 *100 407098573 KS23616 L46
*Install 60-100 ampere circuit breakers in the top level (positions 12-21 and 32-41)
of the distribution panel for a maximum of 10 two-position breakers.
List 23 through 26 Fuse Options
17 -- 406980797 Fuse Holder
18 5 407006329 Fuse, TPA-5
Table 3-H: Field-Installed Components
For List 3 through 6 and 23 through 26 Distribution Panels
Item Size (Amperes) Comcode Description