2 Parameter list
2-3
167 SCPRO % Progress of self-adjustment 0 0 ... 100 26
300 CFCON Current open/closed loop control mode of device VFC
VFC, SFC, FOR VFC = Voltage frequency control
SFC = sensorless speed control
FOR = field orientated regulation
22
_18IA Analog inputs
180 FISA0 Function selector analog standard input ISA00 OFF OFF, STR, STL, INV, /STOP,
SADD1, SADD2, E-EXT, RSERR,
MP-UP, MP-DN, CUSEL, FFTB0,
FFTB1, FFTB2, UM0, UM1, /LCW,
/LCCW, SIO, OPTN1, OPTN2,
MAN, 0-10V, SCALE, PM10V,
0-20, 4-20
see 210-FIS00
0-10V = Voltage input 0-10 V
SCALE = Limitation of motor current
(only FISA1)
PM10V = Voltage input -10 ... +10 V
(only FISA0)
0-20 = Current input 0-20 mA
4-20 = Current input 4-20 mA
12
181 FISA1 Function selector analog standard input ISA01 OFF 12
182 F0PX1 Hz Maximum value ISA0 at +10V, CDS 1 50 -1600 ... 1600 3 3
183 F0PN1 Hz Minimum value ISA0 at +0V, CDS 1 0 -1600 ... 1600 3 3
184 F0NX1 Hz Maximum value ISA0 at -10V, CDS 1 0 -1600 ... 1600 3 3
185 F0NN1 Hz Minimum value ISA0 at -0V, CDS 1 0 -1600 ... 1600 3 3
186 F1PX1 Hz Maximum value ISA1 at +10V, CDS 1 50 -1600 ... 1600 3 3
187 F1PN1 Hz Minimum value ISA1 at +0V, CDS 1 0 -1600 ... 1600 3 3
188 AFIL0 ms Filter time constant for analog channel ISA0 3 0 ... 6
2
x
ms, x = 0, 1, 2, ... 6
44
189 AFIL1 ms Filter time constant for analog channel ISA1 3 0 ... 6
2
x
ms, x = 0, 1, 2, ... 6
44
190 F0PX2 Hz Maximum value ISA0 at +10V, CDS 2 50 -1600 ... 1600 3 3
191 F0PN2 Hz Minimum value ISA0 at +0V, CDS 2 0 -1600 ... 1600 3 3
192 IADB0 % Dead-band range ISA0 0.00 0 ... 90 4 4
193 IADB1 % Dead-band range ISA1 0.00 0 ... 90 4 4
194 F0NX2 Hz Maximum value ISA0 at -10V, CDS 2 0 -1600 ... 1600 3 3
no. name unit function factory set your set range of value explanation R W