KEYPAD KP200
2  Parameter list
2-4
195 F0NN2 Hz Minimum value ISA0 at -0V, CDS 2 0 -1600 ... 1600 3 3
196 F1PX2 Hz Maximum value ISA1 at +10V, CDS 2 50 -1600 ... 1600 3 3
197 F1PN2 Hz Minimum value ISA1 at +0V, CDS 2 0 -1600 ... 1600 3 3
_20OA Analog outputs 
200 FOSA0 Function selector for analog output OSA00 ACTF OFF, ACTF, ACTN, APCUR, 
ACCUR, ISA0, ISA1, MTEMP, 
KTEMP, DTEMP, DCV, VMOT, PS, 
PW, ACTT, AACTF, AACTN
ACTF = Actual frequency 
ACTN = Actual speed
APCUR = Apparent current
ACCUR = Active current
ISAx =  Analog reference value
MTEMP = Motor temperature
KTEMP = Heat sink temperature
DTEMP = Device temperature
DCV = DC-link voltage
VMOT = Motor voltage
PS = Apparent power
PW = Active power
ACTT = Actual torque
AACTF= Magnitude of actual fre-
quency
AACTN= Magnitude of actual fre-
quency
12
201 OAMN0 % Minimum value for analog output OSA00 0 -200 ... 200 3 3
202 OAMX0 % Maximum value for analog output OSA00 100 -200 ... 200 3 3
203 OAFI0 ms Filter time constant for OSA00 0 0 ... 6
2
x 
ms, x = 0, 1, 2, ... 6  
33
204 TSCL  Nm Torque (scaling factor) G* G* 3 3
no. name   unit function factory set your set range of value explanation R W