MENU: STEP BY STEP PROCEDURE E3 Modulevel: Level
Screen Action Comment
Configuration
1
3
16
17
18
19
2
1
Poll Adr
xx
14
Loop Mode
(select)
Trim 4
xxxx
1
5
Trim Lvl
xx.x
Trim 20
xxxx
Loop Tst
xx.x mA
Capture
4.00 mA
20
Capture
20.00 mA
New Pass
xxx
22
23
Language
E3 ModHT
Ver xx.xx
24
DispFact
(select)
E
nter HART ID number.
S
elect a HART poll address (0-15). Enter 0 for a single transmitter
installation.
E
nable/Disable
L
oop Current Mode.
I
f enabled, loop current follows the PV; If disabled, loop current is
xed (i.e., multidrop mode).
E
nter value
t
o adjust level reading.
A
llows to compensate for a fixed level deviation.
Fine tune the 4 mA point. Attach a mA meter to the output. If the output does not equal 4.0 mA,
adjust the value on the display to equal 4.00 mA.
F
ine tune the 20 mA point.
A
ttach a mA meter to the output. If the output does not equal
2
0.0 mA, adjust the value on the display to equal 20.00 mA.
E
nter a mA output value.
S
et mA Output to any given value to perform loop test.
Bring liquid level at desired 4 mA point.
P
ress Enter to enter manual setting
m
ode.
P
ress up arrow + Enter
(
simultaneously) to confirm 4 mA level.
Manual setting of 4 mA output signal: free hanging displacer or level
a
t the lowest level.
B
ring liquid level at highest possible
point.
Press Enter to enter manual setting
mode.
Press up arrow + Enter
(simultaneously) to confirm 20 mA level.
N
ote: in case of full span cannot be
r
eached, adjust loop readout to current
l
evel (see at right).
L
evel is ideally brought to match with 20 mA point. If this is not possi-
ble, bring level to the highest possible position (should correspond
with min 8 mA). Attach a mA meter and adjust the loop current via
the keypad (down & up arrows) to match with the calculated mA
value of the current level.
Enter new password. Use arrows to select desired value. Values between 0 and 255.
Select language.
Select «English», «Français», «Deutsch» or «Espagnol».
None, do not adjust.
Factory setting. «Ver» refers to software version.
Advanced diagnostics. See page 15.
No offset
(Offset at 0 cm)
Positive offset
(Offset at 10 cm)
Negative offset
(Offset at -15 cm)
75 cm
100 %
0 %
15 cm
10 cm
20 mA = 75 cm
4 mA = 15 cm
20 mA = 85 cm
4 mA = 25 cm
20 mA = 60 cm
4 mA = 0 cm
OFFSET