EasyManua.ls Logo

Magnetrol E3 Modulevel - Wiring and Connections; Electrical Safety Precautions; Grounding and Shielding Practices; Intrinsically Safe and Explosion Proof Wiring

Magnetrol E3 Modulevel
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4
WIRING
CAUTION: power must be switched OFF before wiring the unit.
–+
I
S
®
I
S
0 %
100 %
Positive supply to (+) terminal
Negative supply to (-) terminal
Shield wire to green grounding screw (resistance to
ground must be < 1 Ω).
Standard shielded twisted
pair cable recommended.
Use certified flameproof cable
gland(s) and cable for Explosion
proof area.
Galvanic Barrier:
(only needed for intrinsically safe units):
Hart
®
:
- ATEX/IEC: max 28,4 V DC @ 94 mA
- FM: max 28,6 V DC @ 140 mA
Foudation Fieldbus™: max 17,5 V DC @ 380 mA
ANALOG I/O
or
DIGITAL I/O
(only for units with HART)
Customer supplied
local current meter
Do not connect shield
Ex
Non Ex
Ex
Non Ex
Ex
Non Ex
IMPORTANT:
The shield wire should only be grounded at ONE side only. It is recommended to connect the shield to ground in the field (at
the transmitter side - as shown above) but connecting in the control room is also allowed.
REMOTE WIRING
Current loop test point
(Hart
®
only)
123456
Integral
terminal board
Remote
terminal board
Integral wiring &
LVDT housings
Remote wiring &
Transmitter housings
Shield wire to green grounding
screw at 1 side only
Match the numbered wires with the
numbers on each terminal block.

Related product manuals