Page 55Version 2023-06-15 Fire damper - FDMR
TPM 140/19
X
110 **
40...400
ØD
min.
Ø
D+80
max. Ø
D+800
40...800
20
110 **
X
In solid ceiling construction - Weichschott system
For connection of following duct → see page 90
EIS 90
* HILTI system can be replaced by a similar system
with the same or higher thickness, density, fire
reaction class, tested according to EN 1366-3.
1 FDMR
2 Solid ceiling construciton
3 Duct
4 Clamp with threaded rod → see pages 87 to 89
Weichschott system HILTI*
5 Mineral wool board - min. density 140 kg/m³ (HILTI CFS-CT B 1S 140/50...)
6 Fire stop coating - th. 1 mm (HILTI CFS-CT...) - coating is overcoated on the support construction and on the damper casing/duct
7
Fire-resistant mastic - (HILTI CFS-S ACR...) fill the gap from both sides of the fire separation construction and around the perimeter of
penetration and damper casing
** min. 110 mm - Conrete
min. 125 mm - Aerated concrete