InstallationandOperationManual
41
Bus_Open Theaddressableloopcircuitisopen
Bus_CrossPower Theaddressableloopcircuitwireiscross
power
NOU_CircuitTrbl Thenotificationappliancecircuitis
malfunctioning(open,short,grounding,etc.)
FieldDevice
Heat_SensingError Theheatdetectorsensinghasanerror
Smoke_Contamination Thechamberofthesmokedetectoris
contaminated
Smoke_SensingError Thechamberofthesmokedetectoris
severelydirtyandcan’tbeused
Init.Device_Duplicate Twoormoredeviceshavethesameaddress
Init.Device_Illegal Thedeviceisworkingonline,butitisnot
configured
Init.Device_Missing Thedeviceisconfigured, butitismissing
Init.Device_WrongType Thedevicetypeisincorrectlyconfigured
Init.Device_Vol.Abnormal Thedevicedetectsabnormallinevoltage
Init.Device_GeneralTrbl Thedevicehasinternalhardwaretrouble
Whenthetroubleconditionhasbeennoted,pressingACKNOWLEDGEbuttonwillsilencethebuzzerandchange
thetroubleLEDtosteadyON.
Thepanelhasa24‐hourS upv/TroubleResoundfunction.Ifthetroubleconditionisnotcorrectedandthe
Supv/TroubleResoundRemindertimerhaselapsed,thepanelwillre‐
annunciatethetroublecondition .
Whentheindicatedtroubleconditionhasbeencleared,thesystemrevertstonormalstandbycondition
automatically.
SupervisoryConditions
Incaseofasupervisorycondition,thesystemsupervisoryLEDactivates(ON–flashing)andthebuzzeractivates
insupervisorypattern.TheLCDnotesthesupervisoryeventandthe
buzzersoundsinsupervisorypattern.
Supervisoryeventcanbeconfiguredaslatchedornon‐latchedbysettingfromthesystemattributeinterface.
Returningtonormalconditionwill notcausethesupervisoryeventtodisappearuntilmanuallyresetifitis