InstallationandOperationManual
63
EOL× 0.00082 0.00082
AuxiliaryPowerSupply Standby Alarm
TotalCurrents Standby Alarm
BatteryCapacity
Table21BatteryCalculation
TotalStandbyCurrent
(fromabove)
HoursofStandbyRequiredperUL864Standard AHforStandby
A x24Hours =
TotalAlarmCurrent
(fromabove)
5MinutesofAlarmOperation
per UL864 Standard, 30 Minutes of Alarm
OperationperULC‐S527and5MinutesofAlert
forTwo‐stage.
AHforAlarm
A
x0.09Hours
(ForULcompliance)
=
A
x0.6Hours
(ForULCcompliance)
=
A.H.forStandby A.H.forAlarm CalculatedA.H. De‐rating
Factor
A.H.RequiredBattery
Capacity
+ = X1.25 =
Maximumavailablebatteryspace:
Length:8.07in.,width:6.61in.,height:7.87in.
Maximumbatterycapacity:40AH
Notes:
Useofalternativebatteriesmayresultinfailureofthepaneltomeetagencyandregulatoryrequirementsand
mayresultinshortenedbatterylife.Batteriesshouldbetestedregularlyandreplacedatleasteveryfouryears.
IftheBatteryTroubleindicatoractivates,therequir edserviceshouldbeperformedby
anauthorizedagent.