28
FIELD
OUTPUT
INPUT
POWER
CT-B
SENSING
VOLTAGE
F-
4
3
F+
GND
CT1
CT2
-1
-12-2-11E1 E2
E3
J2
-10
-3
-11-2
-3
-10-9
-4
-6
-7
-1 -12
-5
-8
CT-A CT-B
CT-C
EXC
OFF
UP
DOWN
DROOP
OFF
VAR/PF
OFF
CGND
AL1AL2
AUX
IN+
AUX
IN-
AUX
CURRENT
LOOP
J1
-1
-2
-3
CAN
HIGH
CAN
LOW
CAN
GND
J3
DVR2000E+ / EC+
GEN
PMG
S2
S3
S1
52B
52
QUICK CONNECT TERMINALS
CAN
Network
10
EXCITER
A
B
C
NOTES:
1. Excitation enabled when switch (S3) is open and disabled when switch is closed.
2. SPDT spring return to center-OFF position type switch (S1) for remote set point adjust.
3. Droop enabled when switch (S2) is open and disabled when switch is closed.
4. Normally-open contact closes in a fault condition.
5. Analog signal input when Auxiliary is configured for control or metering.
6. Should be shorted when Auxiliary is configured for 4-20 mA control or metering.
7. Sensing potential transformer is required if generator output voltage exceeds 600 Volts.
8. VAR/PF regulation enabled when auxiliary contact (52B) is open and disabled when 52B is
closed.
9. Phase B current transformer (CT-B) secondary may be connected to either quick-connect
terminals CT1 and CT2 or J2-2 and J2-11.
10. 120 ohm 0.25 watt resistor required if DVR is a terminal device on CAN backbone.
11. S1, S2, S3, “52” contactor and transfomers supplied by others.
8
3
21
9
4
5
6
7
7.5 uF
370 Vac
Figure 4-8. Typical Connections with Three-Phase Voltage Sensing and Single-Phase Current Sensing
120
Ohm
5
Installation
Figure 5-9. Typical Connections with ABC Rotation, Three-Phase Voltage Sensing and Single-Phase Current Sensing
GPN046 04-13.indd 28 4/5/13 10:24 AM