14
10.2.5 LN Parameters
These parameters are used to link alarm event from inputs or any other source to the telephone
numbers on TN list.
Table of parameters:
Input & telephone No. linking for 1
st
alarm input (TN1 – TN0)
Input & telephone No. linking for 2
st
alarm input (TN1 – TN0)
Power down, telephone No. linking (TN1 – TN0)
Low Battery, telephone No. Linking (TN1 – TN0)
Periodic test SMS, telephone No. linking (TN1 – TN0)
SIM card refill, telephone No. linking (TN1 – TN0)
Tamper switch, telephone No. linking (TN1 – TN0)
Log status, telephone No. linking (TN1 – TN0)
Table 11: LN parameters
Example:
Direct programming on the SIM card
ZEUS4-MC LITE PROGRAMMING TABLE
Refill SIM – SMS is sent to TN1 & TN2
Input1 is called/sent SMS to TN1 & TN3
Input2 is called/sent SMS to TN1, TN2 & TN3
Periodic Test SMS is sent to TN1 & TN2
Table 12: LN parameters example
Remote programming by SMS
;LN8=12;LN1=13;LN2=123;LN7=12;
10.2.6 MAIN and BATT parameter
ZEUS4-MC LITE can send an SMS message in case of the main power failure. SMS message is
sent to user. You can also program how long the unit can stay without power before sending this
message.
ZEUS4-MC LITE can control battery level and sends 3 SMS messages when following voltage
level on battery is reached: 11.5V, 10.5V and 9V. It sends the “Low Battery” and battery level in
volts SMS message together.