MLI Ultra 12/1250, 24/1250 – User and Installation Manual
25
The Configured Battery Cluster Topology window appears.
7. Enter the number of batteries in series (S). If there are no batteries in series, enter 1.
8. Enter the number of batteries in parallel (P). If there are no batteries in parallel, enter 1.
9. To activate voltage balancing of all cells in series, select ON from the Series Balancing drop-down
list.
10. Click the OK button to return to the Advanced Settings window.
11. Click the OK button to return to the Module Modifications window and then click the Alarm/Switch
Settings button.
12. The Battery Alarm/Switch Settings window appears. To copy these settings from the Primary
battery to all secondary batteries, tick Apply to cluster.
13. Keep clicking OK until all dialog windows have disappeared.
14. Write the configuration to the network to use the new configuration.
To identify the Primary battery, go to the Meters tab. The battery with two DC instances is the Primary
battery.