i-32V5C MIDI Inverter Air/Water chillers with axial fan
5
1. DESCRIPTION OF UNIT AND TECHNICAL SPECIFICATIONS
The refrigerant chillers in this series are designed for residenal and commercial applicaons. The use of brushless inverter compressor technol-
ogy, combined with an electronic expansion valve, circulator and variable speed fan, opmise the consumpon and operang eciency of the
cooling components.
FRAMEWORK
Structure suitable for outdoor installaon consisng of thick proles in hot galvanised sheet metal painted with polyester powder, colour RAL
7035 textured, resistant to atmospheric agents.
The removable panels allow maintenance inside the refrigeraon and hydraulic circuits.
COMPRESSORS
Twin rotary hermec inverter controlled DC compressors, specically designed to operate with R32, equipped with thermal
protecon and mounted on rubber vibraon dampers.
This component is installed in a compartment separate from the air ow to reduce noise and is equipped with a crankcase heater that prevents
the diluon of the oil by the refrigerant, ensuring correct lubricaon and reducing wear on moving parts.
The compressors can be inspected by removing the side and front panels of the unit, allowing maintenance even when the unit is running.
AIR SIDE HEAT EXCHANGER
The air exchangers are made enrely of aluminium using micro-channel technology, which makes it possible to signicantly reduce both the
pressure drops on the air side and the refrigerant charge, at the same me guaranteeing a greater exchange capacity with the same frontal sur-
face area compared to tradional exchangers and a lower refrigerant charge. On request, the coils can have surface treatments to allow greater
resistance to corrosion.
UTILITY SIDE HEAT EXCHANGER
Gli scambiatori possono essere equipaggia di resistenza elerica angelo (accessorio opzionale KA1). Brazed plate heat exchanger made of AISI 304
stainless steel, coated with black exible closed-cell elastomeric foam; thickness 9 mm, thermal conducvity (λ)≤0.036 W/mK (at air +20°C). A ow
switch installed on the water side ensures the presence of water ow and, together with the protecon probe, prevents the formaon of ice inside.
The exchangers can be equipped with an electric anfreeze heater (oponal accessory KA1).
FAN
The fans are axial type with airfoil blades. They are stacally and dynamically balanced and supplied complete with protecon grille and air inlet
and outlet with double ared prole, specially shaped to increase eciency and reduce noise. The electric motor used is driven in modulaon
with brushless EC motor, directly coupled, and equipped with integrated thermal protecon. The motor has an IP 54 protecon rang according
to CEI EN 60529.
COOLING CIRCUIT
The cooling circuit is made of copper piping, brazed and assembled in the factory in accordance with EN 13134. The components present are:
• Filter drier with 100% molecular sieve cartridge;
• Shut-o valve on the liquid line;
• Liquid ow and moisture indicator;
• Electronic expansion valve;
• Charge connecons;
• High-pressure safety pressure switches;
• High and low pressure transducers.
The sucon line is thermally insulated with exible, closed-cell elastomeric foam.
Each unit is pressure tested to check for leaks and is supplied complete with a refrigerant charge opmised for operaon.