i-32V5C MIDI Inverter Air/Water chillers with axial fan
7
• GI module - system management. (oponal or for versions that require it).
The control secon includes:
• Interface terminal with alphanumeric display;
• Display funcon for set values, analogue inputs, fault codes, alarm history and parameter index;
• Key on/o and alarm reset;
• Key combinaons to force defrost and force pump to maximum speed;
• Management of unit start-up from local or remote;
• ModBus connecvity (oponal);
• BMS connecvity via converter
• BMS connecvity provision (ModBus/Bacnet/Knx/Lonworks) - oponal.
CONTROL AND PROTECTIVE DEVICES
All the units are standard supplied with the following control and protecve devices: return water temperature probe, installed on water return
pipe from the plant, working and anfreeze probe installed on the water delivery pipe to the plant, high pressure transducer, low pressure
transducer, inlet and outlet temperature probes from the compressor, compressor thermal protecon, fan thermal protecon, water side ow
switch protecng the evaporator, HP pressure switch.
WATER CIRCUIT
The series units are supplied with a built-in water circuit which includes: modulang circulator with high-eciency brushless motor (EEI≤0.23),
suitable for the use of chilled water and managed directly by the machine’s controller, plate heat exchanger, protecve ow switch, safety valve
(6 bar) to be connected to a collecon system and manual air venng valve.
2. DESCRIPTION OF VERSIONS AND ACCESSORIES
VERSIONS
The available versions are:
i-32V5C Midi - standard version chiller
i-32V5C-DS Midi - chiller with desuperheater
The unit with desuperheater includes the addion of a brazed plate type heat exchanger made of AISI 316 stainless steel, factory insulated using
closed cell material. This version allows to recover about 20% of the condensing heat otherwise lost and to use it to feed the aer-heang water
coils of an AHU or for a hot water ywheel or for any other process use.
i-32V5C-BT Midi - BT version chiller (for low water temperatures)
The BT version unit allows the operang range of the unit to be extended by cooling water to -8°C. In this case, a mixture of water and glycol is
used.
Order code
0110720#
54
Cooling only - BT
3
Desuperheater
0 Without injection
0
4
Exchanger
1
With GI/GI2 plant
3 Modbus (CM) +GI
2
Thermomagnetic
circuit breakers
7
treatment (TR1)
treatment
Accessory 1 Code
CT1
TA
Unit version Thermal capacity Water pipe configuration Antifreeze kit accessory
module
Electrical variantsInjection (LT) Silencing
IV
SIL
AC1
MC
GI
EL3
TR
KA
* Not valid if TA=3
LIST OF ACCESSORIES
Available accessories are indicated below: