i-32V5C MIDI Inverter Air/Water chillers with axial fan
9
Fan silent mode
Digital input that can be acvated by an external contact that allows the reducon of the sound power level by acng on the venlaon. The
mode is parcularly suitable during night operaon. The decreases in capacity and sound power level when the "fan silent mode" funcon is
acve are shown below.
The reducon refers to the test condion (1) of the technical data tables; the value is determined on the basis of measurements carried out in
accordance with UNI EN ISO 9614-2, in compliance with the requirements of Eurovent cercaon.
Model i-32V5C Midi
0121 -1
0126
0128
0132
The treatment consists in the applicaon by spraying of a special water-based paint made of new resins with very high chemical resistance. The
product is exible to resist thermal contracon and expansion, UV resistant, dirt repellent, mechanically resistant, with very low heat transmis-
sion losses and praccally no eect on air-side pressure drops.
The treatment withstands 6000 h according to ASTM B117.
metal grid to prevent the intrusion of foreign bodies inside the coil and to protect the coil from accidental contact with things or people.
KA1
Heat exchanger adhesive resistor - electrical resistor located on the front face of the plate heat exchanger, which is acvated when the tempera-
ture of the water inside the exchanger drops below +4°C. For BT units, this value must be set according to the percentage of glycol in the system
and the freezing point of the mixture.
allows the management of the following funcons:
• Compressor ON/OFF signalling
• General alarm signalling/Machine block signalling
signals if all three phases are present in the correct sequence and if all three phase-to-phase voltages are within the set limits. The maximum and
minimum voltage thresholds can be set separately.
Overcurrent circuit breaker applied upstream of electrical components, protects components from failures caused by current peaks.
input allowing set-point changes.
Acvang this funcon by the procedure described in the controller manual, the unit will reduce the absorbed power by about 10% compared
to the nominal reference value; there will therefore also be a reducon in capacity of the unit.
contains a stainless steel mesh sieve (500 μm ltraon) that collects solids in the water. Filtraon prevents clogging and/or
damage to devices installed downstream of the lter.
system temperature probe to be posioned inside an external tank. The system remote probe thermoregulates the heat pump only during the
compressor start-up phase; shutdown is managed by the probe on the unit's delivery side.
are designed to prevent the transmission of vibraons to the structure; they are mounted underneath the unit in special
holes.
The opmum recommended load capacies are given below, depending on the size of the machine.