i-32V5C MIDI Inverter Air/Water chillers with axial fan
9
Fan silent mode
Digital input that can be acvated by an external contact that allows the reducon of the sound power level by acng on the venlaon. The
mode is parcularly suitable during night operaon. The decreases in capacity and sound power level when the "fan silent mode" funcon is
acve are shown below.
The reducon refers to the test condion (1) of the technical data tables; the value is determined on the basis of measurements carried out in
accordance with UNI EN ISO 9614-2, in compliance with the requirements of Eurovent cercaon.
Model i-32V5C Midi  
0121  -1
0126  
0128  
0132  


The treatment consists in the applicaon by spraying of a special water-based paint made of new resins with very high chemical resistance. The
product is exible to resist thermal contracon and expansion, UV resistant, dirt repellent, mechanically resistant, with very low heat transmis-
sion losses and praccally no eect on air-side pressure drops.
The treatment withstands 6000 h according to ASTM B117.

metal grid to prevent the intrusion of foreign bodies inside the coil and to protect the coil from accidental contact with things or people.
KA1
Heat exchanger adhesive resistor - electrical resistor located on the front face of the plate heat exchanger, which is acvated when the tempera-
ture of the water inside the exchanger drops below +4°C. For BT units, this value must be set according to the percentage of glycol in the system
and the freezing point of the mixture.

allows the management of the following funcons:
Compressor ON/OFF signalling
General alarm signalling/Machine block signalling

signals if all three phases are present in the correct sequence and if all three phase-to-phase voltages are within the set limits. The maximum and
minimum voltage thresholds can be set separately.

Overcurrent circuit breaker applied upstream of electrical components, protects components from failures caused by current peaks.


input allowing set-point changes.

Acvang this funcon by the procedure described in the controller manual, the unit will reduce the absorbed power by about 10% compared
to the nominal reference value; there will therefore also be a reducon in capacity of the unit.


contains a stainless steel mesh sieve (500 μm ltraon) that collects solids in the water. Filtraon prevents clogging and/or
damage to devices installed downstream of the lter.

system temperature probe to be posioned inside an external tank. The system remote probe thermoregulates the heat pump only during the
compressor start-up phase; shutdown is managed by the probe on the unit's delivery side.

are designed to prevent the transmission of vibraons to the structure; they are mounted underneath the unit in special
holes.
The opmum recommended load capacies are given below, depending on the size of the machine.