i-HP Industrial inverter air/water heat pumps with axial fans
25
13.2 LT VERSION
TECHNICAL CHARACTERISTICS
Unit
Models i-HP-LT
0125
0125
Circulator
integrated
0235
0235
Circulator
integrated
0250
0250
Circulator
integrated
Electric data
Power supply
400V/3P+N+T/50Hz
400V/3P+N+T/50Hz
400V/3P+N+T/50Hz
Maximum power input
kW
14,83
15,14
19,16
19,47
28,62
29,09
Maximum current input
A
21,4
21,9
27,7
28,1
41,4
42,1
Cooling
Cooling capacity (1)
kW
30,72
30,67
36,41
36,37
47,78
47,56
Power input (1)
kW
7,29
7,34
8,87
8,91
12,30
12,52
E.E.R. (1)
W/W
4,21
4,18
4,11
4,08
3,88
3,83
Cooling capacity (2)
kW
22,47
22,50
26,88
26,90
37,71
37,60
Power input (2)
kW
7,29
7,26
9,12
9,10
12,72
12,83
E.E.R. (2)
W/W
3,08
3,10
2,95
2,96
2,97
2,93
SEER (5)
W/W
3,93
4,04
3,91
Heating
Heating capacity (3)
kW
25,80
25,80
32,50
32,50
49,01
49,26
Power input (3)
kW
6,17
6,17
7,98
7,98
12,68
12,93
C.O.P. (3)
W/W
4,18
4,18
4,07
4,07
3,87
3,81
Heating capacity (4)
kW
25,67
25,65
32,50
32,50
47,04
47,29
Power input (4)
kW
7,29
7,27
9,97
9,97
14,18
14,40
C.O.P. (4)
W/W
3,52
3,53
3,26
3,26
3,32
3,28
SCOP (6)
W/W
4,02
4,03
3,82
Compressor
Brand
Mitsubishi
Mitsubishi
Mitsubishi
Type
Scroll DC Inverter
Scroll DC Inverter
Scroll DC inverter
Number
1
2
2
Refrigerant oil (type, quantity)
mL
FV50S, 2300 totale
FV50S, 3400 total
FV50S, 4600 total
Fan motor
Type
DC Brushless Motor
DC Brushless Motor
DC Brushless Motor
Number
1
1
1
Rated power input (2)
kW
0,60
0,72
1,10
Max power input
kW
1,45
1,50
1,78
Max current input
A
2,10
2,17
2,57
Speed
r/min
540
580
670
Rated air flow
m3/s
5,00
5,56
6,94
Refrigerant
Type
R410A
R410A
R410A
Refrigerant quantity
kg
10,5
11,2
16,5
Equivalent amount of CO2
ton
21,92
23,39
34,45
Design pressure (high/low)
MPa
4,15/2,7
4,15/2,7
4,15/2,7
Hydraulic circuit
Water flow rate (2)
L/s
1,07
1,07
1,28
1,29
1,80
1,80
Available head pressure (2)
kPa
/
84
/
81
/
65
Internal head loss (2)
kPa
33
34
51
Pump rated power input (2)
kW
/
0,28
/
0,31
/
0,45
Pump max power input
kW
/
0,31
/
0,31
/
0,55
Pump max current input
A
/
1,37
/
1,37
/
2,05
Hydraulic connections
inch
2”F
2”F
2”F
Minimum volume of water (7)
L
90
108
151
Energy Efficiency Index (EEI)
/
≤ 0,23
/
≤ 0,23
/
≤ 0,23
Noise level
Sound power (8)
dB(A)
70,1 / SL 68,3 / SSL 67,4
73,6 / SL 71,8 / SSL 70,9
76,5 / SL 74,5 / SSL 73,6
Sound pressure (9)
dB(A)
54,4 / SL 52,4 / SSL 50,7
56,5 / SL 54,7 / SSL 53,0
59,7 / SL 58,7 / SSL 56,5
Dimensions and
weight
Dimensions (L×H×W)
mm
1198x1673x1198
1198x1673x1198
1198x1745x1198
Packing dimensions (L×H×W) (10)
mm
1200x1765x1200
1200x1765x1200
1200x1890x1200
Operating weight
kg
Peso in
esercizio
kg
373
389
432
Net/Gross weight
kg
Peso
netto/lordo
kg
365/385
371/391
424/444
Operating conditions:
(1) Cooling: Outdoor air temperature 35°C; inlet/outlet temperature 23/18°C.
(2)
Cooling: Outdoor air temperature 35°C; inlet/outlet temperature 12/7°C.
(3)
Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 30/35°C.
(4) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 40/45°C.
(5) Cooling: water temperature inlet/outlet 12/7°C.
(6) Heating: normal climatic condition; Tbiv=-7°C; eater temperature inlet/outlet 30/35°C.
(7) Calculated in the case of the plant water temperature decreased by 15°C with 6 minutes of defrosting.
(8) Condition (3); the value is determined on the basis of measurements taken in accordance with the UNI EN ISO 9614-2, in compliance with the requirements of
Eurovent certification.
(9) Sound pressure level measured at 1m from the unit, in free field, according to ISO 3744. Also the values with installed accessories SL or SSL are reported.
(10) Packing height including the pallet
(*) With Hz max operation, this function can be activated by the user.
N.B. The performance data are indicative and could be subject to change. In addition, the performances declared in apex (1), (2), (3) and (4) refer to the
instantaneous power according to EN 14511. The declared data stated in the apex (6) is determined according to the UNI EN 14825.