TROUBLE SHOOTING
7-18
16. “Er8” RS485 communications error
Problem a communications error occurred during RS485 communications.
What to Check and Suggested Measures
1. Host controllers (e.g.
PLCs and personal
computers) did not
operate due to
incorrect settings
and/or defective
Check the controllers.
→ Remove the cause of the controller error.
2. Relay converters (e.g.
RS232C/RS485
converter) did not
operate due to
incorrect connections
and settings, and
Check the converter (e.g. check for poor contact).
→ Change the various converter settings, reconnect the wires, or
replace hardware (such as recommended devices) as appropriate.
communications cable
Check continuity of the cable, contacts and connections.
→ Replace the cable.
response error
detection time (y08)
has been set,
communications did
Check the host controllers.
→ Change the settings of host controller software, or make the no
response error detection time invalid (y08=0).
5. A high intensity noise
was given to the
inverter.
Check if appropriate noise control measures have been implemented
(e.g. correct grounding and routing of control and main circuit wires).
→ Improve noise control.
→ Improve measures against noise from host controllers.
→ Replace the relay converter with a recommended insulated
converter.
communications differ
between the inverter
Compare the settings of the y codes (y01to y10) with those of the host
controllers.
→ Correct any settings which differ.
communications card
→ Replace the card.