High pressure trip
- outdoor unit motor broken
- outdoor circulating air short (cooling)
- outdoor heat exchanger too dirty (cooling)
- outdoor ball valve not open
- indoor circulating air short (heating)
- indoor heat exchanger too dirty (heating)
- indoor unit filter web blocked (heating)
- indoor unit EXV not turn on properly (heating)
- too much refrigerant
- outdoor unit PCB high pressure output port malfunction
- pressure sensor broken
- pressure switch broken
Low pressure trip
- Outdoor ball valve not open
- Outdoor heat exchanger efficiency too low when heating
- Outdoor motor run abnormally when heating
- Refrigerant leakage or insufficient
- Outdoor PCB low pressure output port abnormal
- Low pressure sensor broken
Digital compressor’s operating current too high, overload protector on
Fixed compressor’s operating current too high, overload protector on
High pressure malfunction occur 3 times within 1 hour
Low pressure malfunction occur 3 times within 1 hour
Too high discharge temperature occur once
Compressor overload protector shut and occur 3 times
Examine outdoor unit for error code.
Connect wired controller to the unit to retrieve exact error code.