Ambient temperature is
out of operation limit
range (slave unit)
Ambient temperature is out of operation limit range
1. Cooling ambient temperature range: 0ºC – 43ºC
2. Heating ambient temperature range: -15ºC – 16ºC
Outdoor slave unit circulating air short-circuit
1. Result in ambient temperature raising to exceed operation limit range when cooling
2. Result in ambient temperature falling down to exceed operation limit range when
heating
Digital compressor
overloaded (slave unit)
Fixed compressor 4 operating current too high, overload protector OL4 on
Fixed compressor 1
overloaded (slave unit)
Fixed compressor 1 operating current too high, overload protector OL1 on
Fixed compressor 2
overloaded (slave unit)
Fixed compressor 2 operating current too high, overload protector OL2 on
Fixed compressor 3
overloaded (slave unit)
Fixed compressor 3 operating current too high, overload protector OL3 on
High pressure too high
(slave unit)
Slave unit motor broken
Slave unit circulation air short-circuiting (cooling)
Slave unit heat exchanger too dirty (cooling)
Slave unit ball valve not open
Indoor circulation air short-circuit (heating)
Indoor heat exchanger too dirty (heating)
Indoor unit filter blocked by dirt (heating)
Indoor EXV not switched on properly (heating)
Refrigerant over charged
Slave unit PCB high pressure output port abnormal
Slave unit pressure sensor broken
Slave unit pressure switch broken
High pressure sensor
malfunction (slave unit)
Slave unit high pressure sensor connecting wire broken
Slave unit PCB HS port broken
Discharge temperature
too high (slave unit)
Super heat protecting
value too small (slave
unit)
Indoor motor not work when cooling
Indoor EXV opening degree abnormal when cooling
Outdoor motor not work when heating
Slave unit EXV opening degree abnormal when heating
Slave unit low pressure sensor abnormal
Refrigerant over charged
Low pressure too low
(slave unit)
Slave unit ball valve not open
Slave unit heat exchanger efficiency too low when heating
Slave unit motor run abnormally when heating
Refrigerant leaked or insufficient charged
Slave unit PCB low pressure output port abnormal
Slave unit low pressure sensor broken
Low pressure sensor
broken (slave unit)
Slave unit low pressure sensor connecting wire broken
Slave unit PCB LS port broken