General Information
General Specification
Accuracy Insulation test:
1000 Volts 10 kΩ - 999 MΩ ±3% ±2 digits
500 Volts. 10 kΩ - 500 MΩ ±3% ±2 digits >500 MΩ ±10% ±4 digits
250 Volts. 10 kΩ - 250 MΩ ±3% ±2 digits >250 MΩ ±10% ±4 digits
100 Volts. 10 kΩ - 100 MΩ ±3% ±2 digits >100 MΩ ±10% ±4 digits
EN61557 range: 10 kΩ - 999 MΩ (1000 V range)
Voltage display: ±3% ±3 digits ±0.5% of rated voltage
Max service error: ±15% ±2 digits.
Short circuit current: 1.5 mA nominal test current
Test current on load: ≥1 mA at min. pass values of insulation
Output voltage tolerance: -0% +20% at rated load or less
Continuity / Resistance:
Intrinsic accuracy: ±2% ±2 digits (0.01 Ω to 99.9 Ω) ±5% ±2 digits (100 Ω to 99.9 kΩ)
EN61557 range: 0.1 Ω to 99.9 kΩ
Open circuit voltage 5 V ±1 V
Test current at 200 mA (0 Ω to 2 Ω): >200 mA @ ≤2 Ω
Test current at 15 mA (0 Ω to 2 Ω): >15mA @ ≤2 Ω
Max Service error: ±12% ±2 digits.
GFCI test:
Ramp test current: ±5% ±1 digit
Supply: 48 V - 280 V 45 Hz to 65 Hz
Max service error: ±10% ±2 digits
Voltage:
Intrinsic accuracy: ±2% ±1 V
EN61557-1 Range: 10 V to 600 V
Phase rotation indication.
Max service error: ±5% ±2 digits
Frequency:
Intrinsic accuracy: ±0.5% ±2 digits
Resolution: 0.1 Hz
EN61557 Range: 15 Hz to 400 Hz
Max service error: ±5% ±3 digits
Ground Test Ranges:
Intrinsic accuracy: ±2.0% ±3 digits
ART method ±5.0% ±3 digits
Stakeless method ±7.0% ±3 digits
Resolution: 0.01 Ω
EN61557 range: 1.0 Ω to 1.99 kΩ
Current: 0.45 mA or 4.5 mA.
Noise rejection: 20 V pk/pk (7 V rms)
Max probe resistances: Rp, Rc = 100 kΩ @ 50 V
Max service error: ±20% ±3 digits