Mendota FV41 - ROOF VENTING WITH FOUR 90 DEGREE ELBOWS

Mendota FV41
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32 | Page
H2
H1
V1
FOUR 90° ELBOWS, VERTICAL TERMINATION
2'
4'- 40'
3'
V1(12" MIN.)
12"
H1+H2+H3
5'
24
9'
3'
58'
41'
55'
60'
V2 MAX
H3
V2
VERTICAL THROUGH-THE-ROOF VENTING USING FOUR 90
0
ELBOWS
In extreme situations, Four 90
0
elbows may be required to reach a proper exit point for the vent system. Mendota has
spent considerable time and effort in the design of this fireplace and its venting system. Through this effort, Mendota has
been able to certify the use of Four 90
0
elbows.
The use of Four 90
0
elbows must meet some minimum prerequisites.
Prerequisite #1: The vent system must terminate vertically using a vertical vent cap.
Prerequisite #2: There must be a minimum 12 inches of vertical starter section connected directly to the top of this fire-
place.
Prerequisite #3: For vertical starter sections less than 4 feet tall, you must reduce 6 feet off the maximum horizontal run
allowed per Figure 15 on page 21, Zone A.